Working out cable length and current for a voltage drop check
You need four numbers: the system voltage, the current, the cable length and the drop you'll allow. Two of them cause most of the mistakes. They're current and length.
Length: one way or both ways?
A DC circuit is a loop. Current goes out on the positive cable and comes back on the negative. Both cables lose voltage, so both count.
Charts and formulas handle this in two different ways, and mixing them up gives a wrong answer by a factor of two.
| Chart that counts both cables | Formula that doubles the length itself | |
|---|---|---|
| What you enter | Total of positive and negative cable | One-way distance only |
| Common slip | Entering only the one-way distance | Entering the total, so the length is counted twice |
For the chart route, the maker says to add up both cables1, and its other guide agrees2. The formula route is different. It reads V drop (V) = (2 × L × I × R) / 1000, with L the one-way length1. Read the notes under any chart or calculator and check what its length means.
Current: what number goes in
Current is measured in amps. The aim is the largest current the circuit will carry, not the average.
- For a single appliance, use the rating on its label or in its manual.
- For several loads on one cable, add up what runs at once.
- For an inverter, one maker gives the working: "Maximum Current = Inverter Power ÷ System Voltage"2.
The inverter formula shows why voltage matters. The same power on a lower voltage means more amps.
Putting it together
The first guide gives a worked example. It uses a 12V system and 10 AWG cable. The run is 15 ft one way and the current is 20A. The drop works out to 0.60V1.
To get a percentage, divide the drop by the system voltage. The guide writes it as %V drop = (V drop / System Voltage) × 100%1.
The result is 5.0%. The guide's verdict: "5.0% exceeds the typical 3% limit", so the answer is a thicker cable1.
Which drop limit?
Pick the limit before you start. A tight limit suits equipment that's fussy about voltage. A looser one may do for small, forgiving loads. The wire and fuse sizing guide says the final cable selection should be verified against actual system voltage, cable length and allowable voltage drop2.
A short checklist
- Write down the system voltage.
- Find the highest current the circuit will carry.
- Measure the cable route, following the path it will really take, not a straight line.
- Decide if your chart wants one-way or total length.
- Pick the allowed drop and work through the chart or formula.
Allow for bends, rises and the trip to the fuse and switch. A route measured with string is often longer than one measured by eye.
When you're done, the cable still needs a fuse matched to it. The fuse-matching page covers that step. A number you can't pin down is worth a call to the equipment's maker.
Isolate the battery and follow the equipment maker's manual before any cable is connected or removed. Fixed mains wiring, switchboards and grid connection are licensed electrical work in Australia.