How to read a DC cable size chart
A cable chart is a lookup table. You find your current, find your cable length, and read across to a cable size. The skill is knowing what the chart assumed before you trust the answer.
The three columns
Amps. This is the current the circuit carries. Some charts list the load's current, and others list the fuse rating. One maker's chart is headed by fuse rating, in bands such as 0–20A and 20–30A1. Check which one your chart uses.
Length. This is how far the cable runs. It's the part people get wrong. In the same guide, the length means the total of the positive and negative cables combined1. A second guide from the same maker agrees that both cables count2.
Percent drop. Often this isn't a column at all. It's a note above the table saying how much voltage loss the chart allows. For a 12V system, the first guide's table uses 3%, which it gives as 0.36V1.
Two charts, two answers
Charts are built on different rules, so they don't always agree. Compare them side by side.
| Chart built on a tight limit | Chart built on a looser limit | |
|---|---|---|
| Voltage drop assumed | 3% for a 12V system1 | Less than 8%2 |
| What it suits | Loads that need steady voltage, such as an inverter | Cases where a larger drop is tolerable |
| Cable size for the same job | Often thicker | Often thinner |
The second chart states its assumption directly: "The table assumes a voltage drop of less than 8%"2. Neither chart is wrong. They answer different questions, and the allowed drop is what changes the answer.
A worked read
Take the first chart and a circuit with a fuse in the 0–20A band. For a run of 0–10 ft, or 0–3 m, the chart gives 12 AWG / 3.31 mm²1. Move to the 20–30A band at the same length and the answer becomes 10 AWG / 5.26 mm²1.
So a bigger current, at the same length, calls for a thicker cable. You'll see the same pattern as you move right along a row: more length, thicker cable.
Things to check before you trust a chart
- What voltage drop does it assume?
- Is the current the load's current or the fuse rating?
- Is the length one way or both ways?
- What cable type, temperature rating and layout does it assume?
- Does it say anything about bundled cables or hot spaces?
The guide itself says the final choice should be verified against your actual system voltage, cable length and allowable drop2. A chart is a starting point.
Unsure? Ask the equipment maker or a qualified installer. Isolate the battery and follow the maker's manual before touching any connection. Mains wiring is a job for a licensed electrician.
Related pages cover cable size units and the numbers you'll type into a chart.